Water Treatment Unit / PID-3301 Disinfection, storage and distribution
SVG
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 A A B B C C D D E E F F NOTES 1. Free chlorine target 0.8 mg/L leaving the reservoir. 2. Distribution pumps run on variable speed to hold header pressure (PIC-3304). INSTRUMENT SYMBOLS Field mounted Control system (DCS), operator can see it Electric signal Main process line Utility / secondary line ENTHRA LABS DEMO DRAWING WATER TREATMENT UNIT PIPING AND INSTRUMENT DIAGRAM: DISINFECTION, STORAGE AND DISTRIBUTION DRAWING NO. PID-3301 SHEET / REV 3 OF 4 REV 0 SCALE: NONE DATE: 2026-11-24 FICTIONAL PLANT FOR DEMONSTRATION. NOT FOR CONSTRUCTION. UV UV-3301 UV DISINFECTION UNIT TK-3301 TREATED WATER RESERVOIR P-3301A DISTRIBUTION PUMP P-3301B DISTRIBUTION PUMP (SPARE) PID-3201 FROM TK-3201 14"-TW-3204-C10 14"-TW-3301-C10 PID-3401 FROM P-3402 1"-CH-3402-P10 14"-TW-3302-C10 14"-TW-3303-C10 B/L DISTRIBUTION 12"-TW-3304-C10 B/L DISTRIBUTION 12"-TW-3305-C10 AT 3301 0-100 % UVT LT 3301 LIC 3301 AT 3302 0-5 mg/L Cl2 AIC 3302 0.8 mg/L PT 3304 PIC 3304 5 barg