TK-2002

Peroxide storage tank B
Storage tank
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 A A B B C C D D E E F F NOTES 1. Peroxide tanks must vent freely. Decomposition gives off oxygen and heat. Alarm on temperature rise above 35 C. 2. Batch loading set by FQIC-2004. Driver confirms earthing before loading starts. INSTRUMENT SYMBOLS Field mounted Control system (DCS), operator can see it Electric signal Main process line Utility / secondary line ENTHRA LABS DEMO DRAWING SUGAR TO HYDROGEN PEROXIDE PIPING AND INSTRUMENT DIAGRAM: PEROXIDE STORAGE AND LOADING DRAWING NO. PID-2001 SHEET / REV 10 OF 15 REV 0 SCALE: NONE DATE: 2026-11-24 FICTIONAL PLANT FOR DEMONSTRATION. NOT FOR CONSTRUCTION. TK-2001 PEROXIDE STORAGE TANK A TK-2002 PEROXIDE STORAGE TANK B TK-2003 STABILISER TANK D P-2003 STABILISER DOSING PUMP P-2001 LOADING PUMP PID-1901 FROM E-1903 1"-PR-1909-A10 PID-1901 FROM E-1903 1"-PR-2001-A10 3"-PR-2002-A10 3"-PR-2003-A10 B/L TRUCK LOADING S FV-2004 3"-PR-2004-A10 0.5"-CH-2005-P10 0.5"-CH-2006-P10 ATM PSV-2001 SET 0.05 barg ATM PSV-2002 SET 0.05 barg LT 2001 LAH 2001 90 % TT 2001 0-60 C LT 2002 LAH 2002 90 % TT 2002 0-60 C FQ 2004 FQIC 2004
Design and operating data
Capacity150 m3
ContentsHydrogen peroxide 50 wt%
MaterialAluminium 5254
Design temp40 C
Design pressureATM
Notes
History
No changes recorded.