Plants / Sugar to Hydrogen Peroxide / Live Twin
Live Twin
The plant's sensor data, matched to the drawings and checked against the physics: equipment losing performance, sensors that are stuck or wrong, and upsets.
Sensors matched to the drawings
71
every name matched
Readings
4,032
11/10/2026 to 11/23/2026
Findings
4
2 need attention now
Model vs meters
47.6%
median flow error, was 49.2% before calibrating
Health watch
Stuck sensorFT-1801 has not changed for 48 hours. The transmitter is probably stuck: check it before trusting its reading.On drawing
Sensor disagrees with physicsPT-1405 disagrees with PT-1504: the gap between them grew by 0.38 bar while the plant ran the same. Physics says they should move together, so PT-1405 is probably drifting.On drawing
Equipment losing performanceE-1401 is losing heat transfer: its outlet is +5.5 C warmer than two weeks ago (roughly 11% less heat removed). Plan a clean.On drawing
UpsetAT-1502 went to 4.47 (normally 5.80) on Nov 19 00:30 for about 2.1 hours, then recovered.On drawing
Dashboards by area
PID-1101 Sugar receiving and storagePID-1201 Feed preparationPID-1301 Enzyme and caustic dosingPID-1401 Process air supplyPID-1501 Enzyme reactor 1PID-1601 Enzyme reactor 2PID-1701 Enzyme recovery (ultrafiltration)PID-1801 Peroxide separation (vacuum evaporation)PID-1901 Peroxide concentration (distillation)PID-2001 Peroxide storage and loadingPID-2101 Catalytic oxidationPID-2201 Acid concentration and crystallisationPID-2301 Crystal separation, drying and packingPID-2401 Cooling water systemPID-2501 Steam and condensate
LT-110145.11
min 44.14 · max 46.48
TT-110136.33
min 34.25 · max 36.33
LT-110244.34
min 43.31 · max 45.81
Calibration
Feeds scaled by 1.15 so calculated flows match the meters (median of measured/calculated).
| Sensor | Measured | Model | Model, calibrated |
|---|---|---|---|
| TT-1101 | 35.2 C | 55 | |
| TT-1204 | 40 C | 40 | |
| FT-1205 | 41.99 m3/h | 26.72 | 30.83 |
| TT-1404 | 41 C | 35 | |
| TT-1501 | 30 C | 30 | |
| FT-1503 | 21.09 Nm3/h | 0 | |
| TT-1601 | 30 C | 30 | |
| FT-1603 | 20.5 Nm3/h | 2083.99 | 2404.27 |
| FT-1703 | 14.19 m3/h | 26.95 | 31.09 |
| TT-1801 | 45 C | 45 | |
| FT-1801 | 21.85 m3/h | 26.95 | 31.09 |
| TT-1902 | 43.9 C | 40.5 | |
| FT-1904 | 19.44 m3/h | 7.92 | 9.14 |
| FT-1901 | 15.46 m3/h | 10.33 | 11.91 |
| TT-2001 | 26.5 C | 37.2 | |
| TT-2002 | 29.9 C | 37.2 | |
| FT-2102 | 24.89 m3/h | 15.15 | 17.48 |
| TT-2103 | 70 C | 70 | |
| TT-2105 | 29.7 C | 70 | |
| FT-2104 | 20.33 Nm3/h | 5340.43 | 6161.18 |
| TT-2205 | 15 C | 15 | |
| TT-2307 | 85 C | 32.3 | |
| TT-2401 | 29.3 C | 28.3 | |
| TT-2402 | 35 C | 30.1 |
Daily summary
Enthra daily summary for Sugar to Hydrogen Peroxide, Monday 23 November 2026 - FT-1801 has not changed for 48 hours. The transmitter is probably stuck: check it before trusting its reading. - PT-1405 disagrees with PT-1504: the gap between them grew by 0.38 bar while the plant ran the same. Physics says they should move together, so PT-1405 is probably drifting. - E-1401 is losing heat transfer: its outlet is +5.5 C warmer than two weeks ago (roughly 11% less heat removed). Plan a clean. - AT-1502 went to 4.47 (normally 5.80) on Nov 19 00:30 for about 2.1 hours, then recovered. Open the Live Twin page for trends and details.