Live Twin

The plant's sensor data, matched to the drawings and checked against the physics: equipment losing performance, sensors that are stuck or wrong, and upsets.

Sensors matched to the drawings
71
every name matched
Readings
4,032
11/10/2026 to 11/23/2026
Findings
4
2 need attention now
Model vs meters
47.6%
median flow error, was 49.2% before calibrating

Health watch

Stuck sensorFT-1801 has not changed for 48 hours. The transmitter is probably stuck: check it before trusting its reading.On drawing
Sensor disagrees with physicsPT-1405 disagrees with PT-1504: the gap between them grew by 0.38 bar while the plant ran the same. Physics says they should move together, so PT-1405 is probably drifting.On drawing
Equipment losing performanceE-1401 is losing heat transfer: its outlet is +5.5 C warmer than two weeks ago (roughly 11% less heat removed). Plan a clean.On drawing
UpsetAT-1502 went to 4.47 (normally 5.80) on Nov 19 00:30 for about 2.1 hours, then recovered.On drawing

Dashboards by area

LT-240161.23
min 60.32 · max 63.25
AT-24011524.02
min 1456.97 · max 1537.78
TT-240129.43
min 28.46 · max 30.02
PT-24013.33
min 3.21 · max 3.49
TT-240234.62
min 34.02 · max 35.93

Calibration

Feeds scaled by 1.15 so calculated flows match the meters (median of measured/calculated).

SensorMeasuredModelModel, calibrated
TT-110135.2 C55
TT-120440 C40
FT-120541.99 m3/h26.7230.83
TT-140441 C35
TT-150130 C30
FT-150321.09 Nm3/h0
TT-160130 C30
FT-160320.5 Nm3/h2083.992404.27
FT-170314.19 m3/h26.9531.09
TT-180145 C45
FT-180121.85 m3/h26.9531.09
TT-190243.9 C40.5
FT-190419.44 m3/h7.929.14
FT-190115.46 m3/h10.3311.91
TT-200126.5 C37.2
TT-200229.9 C37.2
FT-210224.89 m3/h15.1517.48
TT-210370 C70
TT-210529.7 C70
FT-210420.33 Nm3/h5340.436161.18
TT-220515 C15
TT-230785 C32.3
TT-240129.3 C28.3
TT-240235 C30.1

Daily summary

Enthra daily summary for Sugar to Hydrogen Peroxide, Monday 23 November 2026

- FT-1801 has not changed for 48 hours. The transmitter is probably stuck: check it before trusting its reading.
- PT-1405 disagrees with PT-1504: the gap between them grew by 0.38 bar while the plant ran the same. Physics says they should move together, so PT-1405 is probably drifting.
- E-1401 is losing heat transfer: its outlet is +5.5 C warmer than two weeks ago (roughly 11% less heat removed). Plan a clean.
- AT-1502 went to 4.47 (normally 5.80) on Nov 19 00:30 for about 2.1 hours, then recovered.

Open the Live Twin page for trends and details.