Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
E-1601 off-gas condenser
PID-1601 · · feed about 10.2 m3/h (quick simulation)
No flowDraft
Causes
  • Hand valve on the inlet left closed
Consequences
  • Downstream of E-1601 runs short of feed
Safeguards
None on the drawings
Action
  • Consider a low flow or low level alarm on E-1601
More flowDraft
Causes
  • Upstream pump running faster than normal
Consequences
  • E-1601 cannot keep up (outlet off temperature)
  • Downstream equipment overloaded
Safeguards
None on the drawings
Action
None
High temperatureDraft
Causes
  • Cooling water lost or too warm
  • Cooling water control valve fails closed
Consequences
  • E-1601 overheats
  • Quick simulation, cooling water 5 C warmer: still within limits
Safeguards
None on the drawings
Action
  • Add a high temperature alarm on E-1601
High pressureDraft
Causes
  • Outlet blocked (valve closed)
  • External fire
Consequences
  • E-1601 over its design pressure (not given)
Safeguards
None on the drawings
Action
  • Check whether E-1601 needs a relief valve