Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
HazardProtected by
C-1901 No flow: Downstream of C-1901 runs short of feedFlow control FT-1901, FIC-1901, FT-1904, FIC-1904Show on drawing
C-1901 More flow: C-1901 overfillsFlow control FT-1901, FIC-1901, FT-1904, FIC-1904Show on drawing
C-1901 Reverse flow: Back-flow from C-1901 through the stopped pumpCheck valve on the pump discharge
C-1901 High level: C-1901 overflows or liquid goes into the ventNothing on the drawings
C-1901 Low level: Outlet pump runs dry and is damagedNothing on the drawings
C-1901 High pressure: C-1901 over its design pressure (FV / 3.5 barg)Pressure control PT-1901, PIC-1901Show on drawing
CR-2201 No flow: Downstream of CR-2201 runs short of feedLevel indication LT-2201, LIC-2201Show on drawing
CR-2201 More flow: CR-2201 overfillsLevel control LT-2201, LIC-2201Show on drawing
CR-2201 Reverse flow: Back-flow from CR-2201 through the stopped pumpCheck valve on the pump discharge
CR-2201 High level: CR-2201 overflows or liquid goes into the ventLevel LT-2201, LIC-2201Show on drawing
CR-2201 Low level: Outlet pump runs dry and is damagedLevel LT-2201, LIC-2201Show on drawing
CR-2201 High temperature: CR-2201 overheatsTemperature control TT-2205, TIC-2205Show on drawing
CR-2201 High pressure: CR-2201 over its design pressure (ATM)Nothing on the drawings
E-1201 No flow: Downstream of E-1201 runs short of feedNothing on the drawings
E-1201 More flow: E-1201 cannot keep up (outlet off temperature)Nothing on the drawings
E-1201 Reverse flow: Back-flow from E-1201 through the stopped pumpCheck valve on the pump discharge
E-1201 High temperature: E-1201 outlet too hotNothing on the drawings
E-1201 High pressure: E-1201 over its design pressure (not given)Nothing on the drawings
E-1401 No flow: Downstream of E-1401 runs short of feedNothing on the drawings
E-1401 More flow: E-1401 cannot keep up (outlet off temperature)Nothing on the drawings
E-1401 Reverse flow: Back-flow from E-1401 through the stopped pumpCheck valve on the pump discharge
E-1401 High temperature: E-1401 overheatsNothing on the drawings
E-1401 High pressure: E-1401 over its design pressure (not given)Nothing on the drawings
E-1501 No flow: Downstream of E-1501 runs short of feedNothing on the drawings
E-1501 More flow: E-1501 cannot keep up (outlet off temperature)Nothing on the drawings
E-1501 High temperature: E-1501 overheatsNothing on the drawings
E-1501 High pressure: E-1501 over its design pressure (not given)Nothing on the drawings
E-1601 No flow: Downstream of E-1601 runs short of feedNothing on the drawings
E-1601 More flow: E-1601 cannot keep up (outlet off temperature)Nothing on the drawings
E-1601 High temperature: E-1601 overheatsNothing on the drawings
E-1601 High pressure: E-1601 over its design pressure (not given)Nothing on the drawings
E-1801 No flow: Downstream of E-1801 runs short of feedFlow control FT-1703, FIC-1703, FT-1801, FIC-1801Show on drawing
E-1801 More flow: E-1801 cannot keep up (outlet off temperature)Flow control FT-1703, FIC-1703, FT-1801, FIC-1801Show on drawing
E-1801 High pressure: E-1801 over its design pressure (not given)Nothing on the drawings
E-1802 No flow: Downstream of E-1802 runs short of feedNothing on the drawings
E-1802 More flow: E-1802 cannot keep up (outlet off temperature)Nothing on the drawings
E-1802 High temperature: E-1802 overheatsNothing on the drawings
E-1802 High pressure: E-1802 over its design pressure (not given)Nothing on the drawings
E-1901 No flow: Downstream of E-1901 runs short of feedNothing on the drawings
E-1901 More flow: E-1901 cannot keep up (outlet off temperature)Nothing on the drawings
E-1901 High temperature: E-1901 overheatsNothing on the drawings
E-1901 High pressure: E-1901 over its design pressure (not given)Nothing on the drawings
E-1902 No flow: Downstream of E-1902 runs short of feedNothing on the drawings
E-1902 More flow: E-1902 cannot keep up (outlet off temperature)Nothing on the drawings
E-1902 High temperature: E-1902 outlet too hotTemperature control TT-1902, TIC-1902Show on drawing
E-1902 High pressure: E-1902 over its design pressure (not given)Nothing on the drawings
E-1903 No flow: Downstream of E-1903 runs short of feedNothing on the drawings
E-1903 More flow: E-1903 cannot keep up (outlet off temperature)Nothing on the drawings
E-1903 High pressure: E-1903 over its design pressure (not given)Nothing on the drawings
E-2101 No flow: Downstream of E-2101 runs short of feedFlow control FT-2102, FIC-2102Show on drawing
E-2101 More flow: E-2101 cannot keep up (outlet off temperature)Flow control FT-2102, FIC-2102Show on drawing
E-2101 Reverse flow: Back-flow from E-2101 through the stopped pumpCheck valve on the pump discharge
E-2101 High temperature: E-2101 outlet too hotNothing on the drawings
E-2101 High pressure: E-2101 over its design pressure (not given)Nothing on the drawings
E-2102 No flow: Downstream of E-2102 runs short of feedNothing on the drawings
E-2102 More flow: E-2102 cannot keep up (outlet off temperature)Nothing on the drawings
E-2102 High temperature: E-2102 overheatsNothing on the drawings
E-2102 High pressure: E-2102 over its design pressure (not given)Nothing on the drawings
E-2201 No flow: Downstream of E-2201 runs short of feedNothing on the drawings
E-2201 More flow: E-2201 cannot keep up (outlet off temperature)Nothing on the drawings
E-2201 High pressure: E-2201 over its design pressure (not given)Nothing on the drawings
E-2301 No flow: Downstream of E-2301 runs short of feedNothing on the drawings
E-2301 More flow: E-2301 cannot keep up (outlet off temperature)Nothing on the drawings
E-2301 Reverse flow: Back-flow from E-2301 through the stopped pumpNothing on the drawings
E-2301 High temperature: E-2301 outlet too hotNothing on the drawings
E-2301 High pressure: E-2301 over its design pressure (not given)Nothing on the drawings
EV-1801 No flow: Downstream of EV-1801 runs short of feedFlow control FT-1801, FIC-1801; Level indication LT-1801, LIC-1801Show on drawing
EV-1801 More flow: EV-1801 overfillsLevel control LT-1801, LIC-1801; Flow control FT-1801, FIC-1801Show on drawing
EV-1801 High level: EV-1801 overflows or liquid goes into the ventLevel LT-1801, LIC-1801Show on drawing
EV-1801 Low level: Outlet pump runs dry and is damagedLevel LT-1801, LIC-1801Show on drawing
EV-1801 High temperature: EV-1801 outlet too hotTemperature control TT-1801, TIC-1801Show on drawing
EV-1801 High pressure: EV-1801 over its design pressure (FV / 3.5 barg)Nothing on the drawings
EV-2201 No flow: Downstream of EV-2201 runs short of feedNothing on the drawings
EV-2201 More flow: EV-2201 overfillsNothing on the drawings
EV-2201 Reverse flow: Back-flow from EV-2201 through the stopped pumpCheck valve on the pump discharge
EV-2201 High level: EV-2201 overflows or liquid goes into the ventNothing on the drawings
EV-2201 Low level: Outlet pump runs dry and is damagedNothing on the drawings
EV-2201 High temperature: EV-2201 outlet too hotNothing on the drawings
EV-2201 High pressure: EV-2201 over its design pressure (not given)Pressure control PT-2201, PIC-2201Show on drawing
F-1201 No flow: Downstream of F-1201 runs short of feedFlow control FT-1205, FIC-1205Show on drawing
F-1201 More flow: F-1201 overfillsFlow control FT-1205, FIC-1205Show on drawing
F-1201 High level: F-1201 overflows or liquid goes into the ventNothing on the drawings
F-1201 Low level: Outlet pump runs dry and is damagedNothing on the drawings
F-1201 High pressure: F-1201 over its design pressure (10 barg)Pressure control PDT-1201, PDI-1201Show on drawing
F-1401 No flow: Downstream of F-1401 runs short of feedNothing on the drawings
F-1401 More flow: F-1401 overfillsNothing on the drawings
F-1401 High level: F-1401 overflows or liquid goes into the ventNothing on the drawings
F-1401 Low level: Outlet pump runs dry and is damagedNothing on the drawings
F-1401 High pressure: F-1401 over its design pressure (not given)Pressure control PDT-1401Show on drawing
M-1701 No flow: Downstream of M-1701 runs short of feedFlow control FT-1703, FIC-1703Show on drawing
M-1701 More flow: M-1701 overfillsFlow control FT-1703, FIC-1703Show on drawing
M-1701 Reverse flow: Back-flow from M-1701 through the stopped pumpCheck valve on the pump discharge
M-1701 High level: M-1701 overflows or liquid goes into the ventNothing on the drawings
M-1701 Low level: Outlet pump runs dry and is damagedNothing on the drawings
M-1701 High pressure: M-1701 over its design pressure (10 barg)Pressure control PDT-1701, PDI-1701Show on drawing
R-1501 No flow: Downstream of R-1501 runs short of feedFlow control FT-1205, FIC-1205, FT-1503, FIC-1503; Level indication LT-1501, LIC-1501Show on drawing
R-1501 More flow: R-1501 overfillsLevel control LT-1501, LIC-1501; Flow control FT-1205, FIC-1205, FT-1503, FIC-1503Show on drawing
R-1501 Reverse flow: Back-flow from R-1501 through the stopped pumpCheck valve on the pump discharge
R-1501 High level: R-1501 overflows or liquid goes into the ventLevel LT-1501, LIC-1501; Relief PSV-1501Show on drawing
R-1501 Low level: Outlet pump runs dry and is damagedLevel LT-1501, LIC-1501Show on drawing
R-1501 High temperature: R-1501 overheatsTemperature control TT-1501, TIC-1501; Relief PSV-1501Show on drawing
R-1501 High pressure: R-1501 over its design pressure (3.5 barg)Relief PSV-1501 set 3.5 bargShow on drawing
R-1601 No flow: Downstream of R-1601 runs short of feedFlow control FT-1603, FIC-1603; Level indication LT-1601, LIC-1601Show on drawing
R-1601 More flow: R-1601 overfillsLevel control LT-1601, LIC-1601; Flow control FT-1603, FIC-1603Show on drawing
R-1601 Reverse flow: Back-flow from R-1601 through the stopped pumpCheck valve on the pump discharge
R-1601 High level: R-1601 overflows or liquid goes into the ventLevel LT-1601, LIC-1601; Relief PSV-1601Show on drawing
R-1601 Low level: Outlet pump runs dry and is damagedLevel LT-1601, LIC-1601Show on drawing
R-1601 High temperature: R-1601 overheatsTemperature control TT-1601, TIC-1601; Relief PSV-1601Show on drawing
R-1601 High pressure: R-1601 over its design pressure (3.5 barg)Relief PSV-1601 set 3.5 bargShow on drawing
R-2101 No flow: Downstream of R-2101 runs short of feedFlow control FT-2104, FIC-2104Show on drawing
R-2101 More flow: R-2101 overfillsFlow control FT-2104, FIC-2104Show on drawing
R-2101 High level: R-2101 overflows or liquid goes into the ventRelief PSV-2101Show on drawing
R-2101 Low level: Outlet pump runs dry and is damagedNothing on the drawings
R-2101 High pressure: R-2101 pressure risesRelief PSV-2101 set 10 barg; Pressure control PDT-2101Show on drawing
SI-2301 No flow: Downstream of SI-2301 runs short of feedLevel indication LT-2302, LI-2302Show on drawing
SI-2301 More flow: SI-2301 overfillsLevel control LT-2302, LI-2302Show on drawing
SI-2301 High level: SI-2301 overflows or liquid goes into the ventLevel LT-2302, LI-2302Show on drawing
SI-2301 Low level: Outlet pump runs dry and is damagedLevel LT-2302, LI-2302Show on drawing
SI-2301 High pressure: SI-2301 over its design pressure (not given)Nothing on the drawings
TK-1101 No flow: Downstream of TK-1101 runs short of feedLevel indication LT-1101, LI-1101Show on drawing
TK-1101 More flow: TK-1101 overfillsLevel control LT-1101, LI-1101Show on drawing
TK-1101 High level: TK-1101 overflows or liquid goes into the ventLevel LT-1101, LI-1101Show on drawing
TK-1101 Low level: Outlet pump runs dry and is damagedLevel LT-1101, LI-1101Show on drawing
TK-1101 High pressure: TK-1101 over its design pressure (ATM)Nothing on the drawings
TK-1102 No flow: Downstream of TK-1102 runs short of feedLevel indication LT-1102, LI-1102Show on drawing
TK-1102 More flow: TK-1102 overfillsLevel control LT-1102, LI-1102Show on drawing
TK-1102 High level: TK-1102 overflows or liquid goes into the ventLevel LT-1102, LI-1102Show on drawing
TK-1102 Low level: Outlet pump runs dry and is damagedLevel LT-1102, LI-1102Show on drawing
TK-1102 High pressure: TK-1102 over its design pressure (ATM)Nothing on the drawings
TK-1201 No flow: Downstream of TK-1201 runs short of feedLevel indication LT-1201, LIC-1201Show on drawing
TK-1201 More flow: TK-1201 overfillsLevel control LT-1201, LIC-1201Show on drawing
TK-1201 Reverse flow: Back-flow from TK-1201 through the stopped pumpCheck valve on the pump discharge
TK-1201 High level: TK-1201 overflows or liquid goes into the ventLevel LT-1201, LIC-1201Show on drawing
TK-1201 Low level: Outlet pump runs dry and is damagedLevel LT-1201, LIC-1201Show on drawing
TK-1201 High pressure: TK-1201 over its design pressure (ATM)Nothing on the drawings
TK-1301 No flow: Downstream of TK-1301 runs short of feedLevel indication LT-1301, LI-1301Show on drawing
TK-1301 More flow: TK-1301 overfillsLevel control LT-1301, LI-1301Show on drawing
TK-1301 High level: TK-1301 overflows or liquid goes into the ventLevel LT-1301, LI-1301Show on drawing
TK-1301 Low level: Outlet pump runs dry and is damagedLevel LT-1301, LI-1301Show on drawing
TK-1301 High pressure: TK-1301 over its design pressure (ATM)Nothing on the drawings
TK-1302 No flow: Downstream of TK-1302 runs short of feedLevel indication LT-1302, LI-1302Show on drawing
TK-1302 More flow: TK-1302 overfillsLevel control LT-1302, LI-1302Show on drawing
TK-1302 High level: TK-1302 overflows or liquid goes into the ventLevel LT-1302, LI-1302Show on drawing
TK-1302 Low level: Outlet pump runs dry and is damagedLevel LT-1302, LI-1302Show on drawing
TK-1302 High pressure: TK-1302 over its design pressure (ATM)Nothing on the drawings
TK-1701 No flow: Downstream of TK-1701 runs short of feedLevel indication LT-1701, LIC-1701Show on drawing
TK-1701 More flow: TK-1701 overfillsLevel control LT-1701, LIC-1701Show on drawing
TK-1701 Reverse flow: Back-flow from TK-1701 through the stopped pumpCheck valve on the pump discharge
TK-1701 High level: TK-1701 overflows or liquid goes into the ventLevel LT-1701, LIC-1701Show on drawing
TK-1701 Low level: Outlet pump runs dry and is damagedLevel LT-1701, LIC-1701Show on drawing
TK-1701 High pressure: TK-1701 over its design pressure (ATM)Nothing on the drawings
TK-2001 No flow: Downstream of TK-2001 runs short of feedLevel indication LT-2001, LAH-2001Show on drawing
TK-2001 More flow: TK-2001 overfillsLevel control LT-2001, LAH-2001Show on drawing
TK-2001 Reverse flow: Back-flow from TK-2001 through the stopped pumpCheck valve on the pump discharge
TK-2001 High level: TK-2001 overflows or liquid goes into the ventLevel LT-2001, LAH-2001; Relief PSV-2001Show on drawing
TK-2001 Low level: Outlet pump runs dry and is damagedLevel LT-2001, LAH-2001Show on drawing
TK-2001 High pressure: TK-2001 pressure risesRelief PSV-2001 set 0.05 bargShow on drawing
TK-2002 No flow: Downstream of TK-2002 runs short of feedLevel indication LT-2002, LAH-2002Show on drawing
TK-2002 More flow: TK-2002 overfillsLevel control LT-2002, LAH-2002Show on drawing
TK-2002 High level: TK-2002 overflows or liquid goes into the ventLevel LT-2002, LAH-2002; Relief PSV-2002Show on drawing
TK-2002 Low level: Outlet pump runs dry and is damagedLevel LT-2002, LAH-2002Show on drawing
TK-2002 High pressure: TK-2002 pressure risesRelief PSV-2002 set 0.05 bargShow on drawing
TK-2003 No flow: Downstream of TK-2003 runs short of feedNothing on the drawings
TK-2003 More flow: TK-2003 overfillsNothing on the drawings
TK-2003 High level: TK-2003 overflows or liquid goes into the ventNothing on the drawings
TK-2003 Low level: Outlet pump runs dry and is damagedNothing on the drawings
TK-2003 High pressure: TK-2003 over its design pressure (ATM)Nothing on the drawings
TK-2101 No flow: Downstream of TK-2101 runs short of feedLevel indication LT-2101, LIC-2101Show on drawing
TK-2101 More flow: TK-2101 overfillsLevel control LT-2101, LIC-2101Show on drawing
TK-2101 Reverse flow: Back-flow from TK-2101 through the stopped pumpCheck valve on the pump discharge
TK-2101 High level: TK-2101 overflows or liquid goes into the ventLevel LT-2101, LIC-2101Show on drawing
TK-2101 Low level: Outlet pump runs dry and is damagedLevel LT-2101, LIC-2101Show on drawing
TK-2101 High pressure: TK-2101 over its design pressure (ATM)Nothing on the drawings
TK-2301 No flow: Downstream of TK-2301 runs short of feedLevel indication LT-2301, LIC-2301Show on drawing
TK-2301 More flow: TK-2301 overfillsLevel control LT-2301, LIC-2301Show on drawing
TK-2301 High level: TK-2301 overflows or liquid goes into the ventLevel LT-2301, LIC-2301Show on drawing
TK-2301 Low level: Outlet pump runs dry and is damagedLevel LT-2301, LIC-2301Show on drawing
TK-2301 High pressure: TK-2301 over its design pressure (ATM)Nothing on the drawings
TK-2501 No flow: Downstream of TK-2501 runs short of feedLevel indication LT-2501, LIC-2501Show on drawing
TK-2501 More flow: TK-2501 overfillsLevel control LT-2501, LIC-2501Show on drawing
TK-2501 High level: TK-2501 overflows or liquid goes into the ventLevel LT-2501, LIC-2501Show on drawing
TK-2501 Low level: Outlet pump runs dry and is damagedLevel LT-2501, LIC-2501Show on drawing
TK-2501 High pressure: TK-2501 over its design pressure (ATM)Nothing on the drawings
V-1401 No flow: Downstream of V-1401 runs short of feedLevel indication LSH-1401, LY-1401Show on drawing
V-1401 More flow: V-1401 overfillsLevel control LSH-1401, LY-1401Show on drawing
V-1401 High level: V-1401 overflows or liquid goes into the ventLevel LSH-1401, LY-1401Show on drawing
V-1401 Low level: Outlet pump runs dry and is damagedLevel LSH-1401, LY-1401Show on drawing
V-1401 High pressure: V-1401 over its design pressure (7 barg)Nothing on the drawings
V-1402 No flow: Downstream of V-1402 runs short of feedFlow control FT-1503, FIC-1503, FT-1603, FIC-1603, FT-2104, FIC-2104Show on drawing
V-1402 More flow: V-1402 overfillsFlow control FT-1503, FIC-1503, FT-1603, FIC-1603, FT-2104, FIC-2104Show on drawing
V-1402 High level: V-1402 overflows or liquid goes into the ventNothing on the drawings
V-1402 Low level: Outlet pump runs dry and is damagedNothing on the drawings
V-1402 High pressure: V-1402 over its design pressure (7 barg)Pressure control PT-1405Show on drawing
V-1802 No flow: Downstream of V-1802 runs short of feedLevel indication LT-1802, LIC-1802Show on drawing
V-1802 More flow: V-1802 overfillsLevel control LT-1802, LIC-1802Show on drawing
V-1802 High level: V-1802 overflows or liquid goes into the ventLevel LT-1802, LIC-1802Show on drawing
V-1802 Low level: Outlet pump runs dry and is damagedLevel LT-1802, LIC-1802Show on drawing
V-1802 High pressure: V-1802 over its design pressure (FV / 3.5 barg)Pressure control PT-1802, PIC-1802Show on drawing
V-1901 No flow: Downstream of V-1901 runs short of feedLevel indication LT-1901, LIC-1901Show on drawing
V-1901 More flow: V-1901 overfillsLevel control LT-1901, LIC-1901Show on drawing
V-1901 High level: V-1901 overflows or liquid goes into the ventLevel LT-1901, LIC-1901Show on drawing
V-1901 Low level: Outlet pump runs dry and is damagedLevel LT-1901, LIC-1901Show on drawing
V-1901 High pressure: V-1901 over its design pressure (FV / 3.5 barg)Nothing on the drawings
V-2101 No flow: Downstream of V-2101 runs short of feedLevel indication LT-2101B, LIC-2102Show on drawing
V-2101 More flow: V-2101 overfillsLevel control LT-2101B, LIC-2102Show on drawing
V-2101 High level: V-2101 overflows or liquid goes into the ventLevel LT-2101B, LIC-2102Show on drawing
V-2101 Low level: Outlet pump runs dry and is damagedLevel LT-2101B, LIC-2102Show on drawing
V-2101 High pressure: V-2101 over its design pressure (10 barg)Pressure control PT-2108, PIC-2108Show on drawing