Safety Studio

Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
Could be over-pressured, and no relief valve on the drawings
C-1901: design FV / 3.5 barg, but a feed pump can reach about 5.5 bar against a closed outlet.
PSV-1501 protects R-1501 · set 3.5 barg · design 3.5 barg
Needs a check
Valve size is not on the drawing or data sheet: add the orifice letter to confirm it is big enough.
Fire around the vesselworst3,765 kg/hAPI 521 heat input Q = 21,000 F A^0.82 (F = 1, wetted area 1335 ft2 up to 7.6 m) = 2,248 kW, boiling water off at 2150 kJ/kg
Blocked outlet900 kg/hall pumps feeding R-1501 at full design flow, 1 m3/h of liquid
Cooling failure1,465 kg/hreaction heat 875 kW (assumed 25 kJ/kg of feed) boils off liquid
Needs about 1,385 mm2 of orifice, API letter L. API 520: A = W / (C K P1 Kb) x sqrt(T Z / M) with W 3,765 kg/h, P1 486 kPa abs (10% over set), T 373 K, M 18, C 0.0261, K 0.975
PSV-1601 protects R-1601 · set 3.5 barg · design 3.5 barg
Needs a check
Valve size is not on the drawing or data sheet: add the orifice letter to confirm it is big enough.
Fire around the vessel3,765 kg/hAPI 521 heat input Q = 21,000 F A^0.82 (F = 1, wetted area 1335 ft2 up to 7.6 m) = 2,248 kW, boiling water off at 2150 kJ/kg
Blocked outletworst48,000 kg/hall pumps feeding R-1601 at full design flow, 48 m3/h of liquid
Cooling failure488 kg/hreaction heat 292 kW (assumed 25 kJ/kg of feed) boils off liquid
Needs about 17,657 mm2 of orifice, API letter larger than T: use two valves. API 520: A = W / (C K P1 Kb) x sqrt(T Z / M) with W 48,000 kg/h, P1 486 kPa abs (10% over set), T 373 K, M 18, C 0.0261, K 0.975
PSV-2001 protects TK-2001 · set 0.05 barg · design ATM
Needs a check
Valve size is not on the drawing or data sheet: add the orifice letter to confirm it is big enough.
Fire around the vesselworst3,391 kg/hAPI 521 heat input Q = 21,000 F A^0.82 (F = 1, wetted area 1175 ft2 up to 7.6 m) = 2,025 kW, boiling water off at 2150 kJ/kg
Blocked outlet20 kg/hall pumps feeding TK-2001 at full design flow, 0 m3/h of liquid
Needs about 5,680 mm2 of orifice, API letter Q. API 520: A = W / (C K P1 Kb) x sqrt(T Z / M) with W 3,391 kg/h, P1 107 kPa abs (10% over set), T 373 K, M 18, C 0.0261, K 0.975
PSV-2002 protects TK-2002 · set 0.05 barg · design ATM
Needs a check
Valve size is not on the drawing or data sheet: add the orifice letter to confirm it is big enough.
Fire around the vesselworst3,391 kg/hAPI 521 heat input Q = 21,000 F A^0.82 (F = 1, wetted area 1175 ft2 up to 7.6 m) = 2,025 kW, boiling water off at 2150 kJ/kg
Needs about 5,680 mm2 of orifice, API letter Q. API 520: A = W / (C K P1 Kb) x sqrt(T Z / M) with W 3,391 kg/h, P1 107 kPa abs (10% over set), T 373 K, M 18, C 0.0261, K 0.975
PSV-2101 protects R-2101 · set 10 barg · design 10 barg
Needs a check
Valve size is not on the drawing or data sheet: add the orifice letter to confirm it is big enough.
Fire around the vesselworst992 kg/hAPI 521 heat input Q = 21,000 F A^0.82 (F = 1, wetted area 262 ft2 up to 7.6 m) = 592 kW, boiling water off at 2150 kJ/kg
Needs about 148 mm2 of orifice, API letter F. API 520: A = W / (C K P1 Kb) x sqrt(T Z / M) with W 992 kg/h, P1 1201 kPa abs (10% over set), T 373 K, M 18, C 0.0261, K 0.975
PSV-2501 protects B-2501 · set 11 barg · design not given
Needs a check
Valve size is not on the drawing or data sheet: add the orifice letter to confirm it is big enough.
Fire around the vessel795 kg/hAPI 521 heat input Q = 21,000 F A^0.82 (F = 1, wetted area 200 ft2 up to 7.6 m) = 475 kW, boiling water off at 2150 kJ/kg
Blocked outletworst10,000 kg/hall pumps feeding B-2501 at full design flow, 10 m3/h of liquid
Needs about 1,364 mm2 of orifice, API letter L. API 520: A = W / (C K P1 Kb) x sqrt(T Z / M) with W 10,000 kg/h, P1 1311 kPa abs (10% over set), T 373 K, M 18, C 0.0261, K 0.975