Plants / Sugar to Hydrogen Peroxide / Safety
Safety Studio
Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.
Safety actions70 open · 0 overdue · 0 done
E-1201Consider a low flow or low level alarm on E-1201
E-1201Add a high temperature alarm on E-1201
E-1201Check whether E-1201 needs a relief valve
F-1201No level measurement on F-1201: add a level transmitter with high alarm
F-1201Add a low level trip to protect the outlet pump of F-1201
F-1201Check whether F-1201 needs a relief valve
F-1401Consider a low flow or low level alarm on F-1401
F-1401Add a high level alarm on F-1401
F-1401No level measurement on F-1401: add a level transmitter with high alarm
F-1401Add a low level trip to protect the outlet pump of F-1401
F-1401Check whether F-1401 needs a relief valve
E-1401Consider a low flow or low level alarm on E-1401
E-1401Add a high temperature alarm on E-1401
E-1401Check whether E-1401 needs a relief valve
V-1401Check whether V-1401 needs a relief valve
V-1402No level measurement on V-1402: add a level transmitter with high alarm
V-1402Add a low level trip to protect the outlet pump of V-1402
V-1402Check whether V-1402 needs a relief valve
E-1501Consider a low flow or low level alarm on E-1501
E-1501Add a high temperature alarm on E-1501
E-1501Check whether E-1501 needs a relief valve
E-1601Consider a low flow or low level alarm on E-1601
E-1601Add a high temperature alarm on E-1601
E-1601Check whether E-1601 needs a relief valve
M-1701No level measurement on M-1701: add a level transmitter with high alarm
M-1701Add a low level trip to protect the outlet pump of M-1701
M-1701Check whether M-1701 needs a relief valve
E-1801Check whether E-1801 needs a relief valve
EV-1801Check whether EV-1801 needs a relief valve
E-1802Consider a low flow or low level alarm on E-1802
E-1802Add a high temperature alarm on E-1802
E-1802Check whether E-1802 needs a relief valve
V-1802Check whether V-1802 needs a relief valve
C-1901No level measurement on C-1901: add a level transmitter with high alarm
C-1901Add a low level trip to protect the outlet pump of C-1901
C-1901No relief valve on C-1901 and the feed pump can exceed its design pressure: add relief
E-1901Consider a low flow or low level alarm on E-1901
E-1901Add a high temperature alarm on E-1901
E-1901Check whether E-1901 needs a relief valve
V-1901Check whether V-1901 needs a relief valve
E-1902Consider a low flow or low level alarm on E-1902
E-1902Check whether E-1902 needs a relief valve
E-1903Consider a low flow or low level alarm on E-1903
E-1903Check whether E-1903 needs a relief valve
TK-2003Consider a low flow or low level alarm on TK-2003
TK-2003Add a high level alarm on TK-2003
TK-2003No level measurement on TK-2003: add a level transmitter with high alarm
TK-2003Add a low level trip to protect the outlet pump of TK-2003
E-2101Add a high temperature alarm on E-2101
E-2101Check whether E-2101 needs a relief valve
R-2101No level measurement on R-2101: add a level transmitter with high alarm
R-2101Add a low level trip to protect the outlet pump of R-2101
E-2102Consider a low flow or low level alarm on E-2102
E-2102Add a high temperature alarm on E-2102
E-2102Check whether E-2102 needs a relief valve
V-2101Check whether V-2101 needs a relief valve
EV-2201Consider a low flow or low level alarm on EV-2201
EV-2201Add a high level alarm on EV-2201
EV-2201No level measurement on EV-2201: add a level transmitter with high alarm
EV-2201Add a low level trip to protect the outlet pump of EV-2201
EV-2201Add a high temperature alarm on EV-2201
EV-2201Check whether EV-2201 needs a relief valve
E-2201Consider a low flow or low level alarm on E-2201
E-2201Check whether E-2201 needs a relief valve
CR-2201Check whether CR-2201 needs a relief valve
E-2301Consider a low flow or low level alarm on E-2301
E-2301No check valve found after B-2301: add one
E-2301Add a high temperature alarm on E-2301
E-2301Check whether E-2301 needs a relief valve
SI-2301Check whether SI-2301 needs a relief valve
Review dates
No signed-off sections yet. Each signed section is due for review again in 5 years.