Safety Studio

Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
E-2101 feed preheater
PID-2101 · · feed about 14.6 m3/h (quick simulation)
No flowDraft
Causes
  • P-2101 stops
  • FV-2102 fails closed
  • TV-2103 fails closed
  • Hand valve on the inlet left closed
Consequences
  • Downstream of E-2101 runs short of feed
  • Quick simulation, P-2101 stopped: 40 lines change flow
Safeguards
  • Flow control FT-2102, FIC-2102
Action
None
More flowDraft
Causes
  • FV-2102 fails open
  • TV-2103 fails open
Consequences
  • E-2101 cannot keep up (outlet off temperature)
  • Downstream equipment overloaded
Safeguards
  • Flow control FT-2102, FIC-2102
Action
None
Reverse flowDraft
Causes
  • P-2101 stops while E-2101 is under pressure
Consequences
  • Back-flow from E-2101 through the stopped pump
Safeguards
  • Check valve on the pump discharge
Action
None
High temperatureDraft
Causes
  • Steam control valve fails open
Consequences
  • E-2101 outlet too hot
  • Heat-sensitive product damaged
Safeguards
None on the drawings
Action
  • Add a high temperature alarm on E-2101
High pressureDraft
Causes
  • Outlet blocked (valve closed)
  • Pump pushing against a closed outlet (9.8 bar at shut-off)
  • External fire
Consequences
  • E-2101 over its design pressure (not given)
Safeguards
None on the drawings
Action
  • Check whether E-2101 needs a relief valve