Plants / Sugar to Hydrogen Peroxide / Safety
Safety Studio
Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.
TK-1101 dextrose syrup storage tank a0/5
PID-1101
TK-1102 dextrose syrup storage tank b0/5
PID-1101
E-1201 feed heater0/5
PID-1201
F-1201 feed sterile filter0/5
PID-1201
TK-1201 feed mix tank0/6
PID-1201
TK-1301 enzyme make-up tank0/5
PID-1301
TK-1302 caustic day tank0/5
PID-1301
E-1401 air aftercooler0/5
PID-1401
F-1401 inlet air filter0/5
PID-1401
V-1401 air knockout drum0/5
PID-1401
V-1402 air receiver0/5
PID-1401
E-1501 off-gas condenser0/4
PID-1501
R-1501 enzyme reactor 10/7
PID-1501
E-1601 off-gas condenser0/4
PID-1601
R-1601 enzyme reactor 20/7
PID-1601
M-1701 ultrafiltration unit0/6
PID-1701
TK-1701 broth hold tank0/6
PID-1701
E-1801 evaporator preheater0/3
PID-1801
E-1802 vapour condenser0/4
PID-1801
EV-1801 vacuum evaporator0/6
PID-1801
V-1802 condensate drum0/5
PID-1801
C-1901 peroxide distillation column0/6
PID-1901
E-1901 overhead condenser0/4
PID-1901
E-1902 reboiler0/4
PID-1901
E-1903 product cooler0/3
PID-1901
V-1901 reflux drum0/5
PID-1901
TK-2001 peroxide storage tank a0/6
PID-2001
TK-2002 peroxide storage tank b0/5
PID-2001
TK-2003 stabiliser tank0/5
PID-2001
E-2101 feed preheater0/5
PID-2101
E-2102 product cooler0/4
PID-2101
R-2101 catalytic oxidation reactor0/5
PID-2101
TK-2101 oxidation feed tank0/6
PID-2101
V-2101 gas-liquid separator0/5
PID-2101
CR-2201 cooling crystalliser0/7
PID-2201
E-2201 concentrator condenser0/3
PID-2201
EV-2201 acid concentrator0/7
PID-2201
E-2301 dryer air heater0/5
PID-2301
SI-2301 product silo0/5
PID-2301
TK-2301 mother liquor tank0/5
PID-2301
TK-2501 condensate and feed water tank0/5
PID-2501
EV-1801 vacuum evaporator
PID-1801 · operating temp 45 C · design pressure FV / 3.5 barg · operating pressure 0.08 bara · feed about 26 m3/h (quick simulation)
No flowDraft
Causes
- FV-1801 fails closed
- FV-1810 fails closed
- Hand valve on the inlet left closed
Consequences
- Downstream of EV-1801 runs short of feed
- Pumps further on can run dry
Safeguards
- Flow control FT-1801, FIC-1801
- Level indication LT-1801, LIC-1801
Action
None
More flowDraft
Causes
- FV-1801 fails open
- FV-1810 fails open
Consequences
- EV-1801 overfills
- Downstream equipment overloaded
Safeguards
- Level control LT-1801, LIC-1801
- Flow control FT-1801, FIC-1801
Action
None
High levelDraft
Causes
- HV-180104 left closed
- Outlet pump stops
Consequences
- EV-1801 overflows or liquid goes into the vent
- Spill of process liquid
Safeguards
- Level LT-1801, LIC-1801
Action
None
Low levelDraft
Causes
- Feed stops
Consequences
- Outlet pump runs dry and is damaged
Safeguards
- Level LT-1801, LIC-1801
Action
None
High temperatureDraft
Causes
- Steam control valve fails open
Consequences
- EV-1801 outlet too hot
- Heat-sensitive product damaged
Safeguards
- Temperature control TT-1801, TIC-1801
Action
None
High pressureDraft
Causes
- Outlet blocked (valve closed)
- External fire
Consequences
- EV-1801 over its design pressure (FV / 3.5 barg)
Safeguards
None on the drawings
Action
- Check whether EV-1801 needs a relief valve