Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
F-1201 feed sterile filter
PID-1201 · design pressure 10 barg · feed about 24.5 m3/h (quick simulation)
No flowDraft
Causes
  • Hand valve on the inlet left closed
Consequences
  • Downstream of F-1201 runs short of feed
Safeguards
  • Flow control FT-1205, FIC-1205
Action
None
More flowDraft
Causes
  • Upstream pump running faster than normal
Consequences
  • F-1201 overfills
  • Downstream equipment overloaded
Safeguards
  • Flow control FT-1205, FIC-1205
Action
None
High levelDraft
Causes
  • FV-1205 fails closed
  • HV-120107 left closed
  • HV-150101 left closed
  • Outlet pump stops
Consequences
  • F-1201 overflows or liquid goes into the vent
  • Spill of process liquid
Safeguards
None on the drawings
Action
  • No level measurement on F-1201: add a level transmitter with high alarm
Low levelDraft
Causes
  • FV-1205 fails open
  • Feed stops
Consequences
  • Outlet pump runs dry and is damaged
Safeguards
None on the drawings
Action
  • Add a low level trip to protect the outlet pump of F-1201
High pressureDraft
Causes
  • Outlet blocked (valve closed)
  • External fire
Consequences
  • F-1201 over its design pressure (10 barg)
Safeguards
  • Pressure control PDT-1201, PDI-1201
Action
  • Check whether F-1201 needs a relief valve