Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
V-1402 air receiver
PID-1401 · design temp 80 C · design pressure 7 barg
No flowDraft
Causes
  • Hand valve on the inlet left closed
Consequences
  • Downstream of V-1402 runs short of feed
Safeguards
  • Flow control FT-1503, FIC-1503, FT-1603, FIC-1603, FT-2104, FIC-2104
Action
None
More flowDraft
Causes
  • Upstream pump running faster than normal
Consequences
  • V-1402 overfills
  • Downstream equipment overloaded
Safeguards
  • Flow control FT-1503, FIC-1503, FT-1603, FIC-1603, FT-2104, FIC-2104
Action
None
High levelDraft
Causes
  • FV-1503 fails closed
  • FV-1603 fails closed
  • FV-2104 fails closed
  • HV-140102 left closed
  • HV-140103 left closed
  • Outlet pump stops
Consequences
  • V-1402 overflows or liquid goes into the vent
  • Spill of process liquid
Safeguards
None on the drawings
Action
  • No level measurement on V-1402: add a level transmitter with high alarm
Low levelDraft
Causes
  • FV-1503 fails open
  • FV-1603 fails open
  • FV-2104 fails open
  • Feed stops
Consequences
  • Outlet pump runs dry and is damaged
Safeguards
None on the drawings
Action
  • Add a low level trip to protect the outlet pump of V-1402
High pressureDraft
Causes
  • Outlet blocked (valve closed)
  • External fire
Consequences
  • V-1402 over its design pressure (7 barg)
Safeguards
  • Pressure control PT-1405
Action
  • Check whether V-1402 needs a relief valve