Safety Studio

Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
V-1901 reflux drum
PID-1901 · design pressure FV / 3.5 barg · feed about 8 m3/h (quick simulation)
No flowDraft
Causes
  • Hand valve on the inlet left closed
Consequences
  • Downstream of V-1901 runs short of feed
  • Pumps further on can run dry
Safeguards
  • Level indication LT-1901, LIC-1901
Action
None
More flowDraft
Causes
  • Upstream pump running faster than normal
Consequences
  • V-1901 overfills
  • Downstream equipment overloaded
Safeguards
  • Level control LT-1901, LIC-1901
Action
None
High levelDraft
Causes
  • HV-190101 left closed
  • Outlet pump stops
Consequences
  • V-1901 overflows or liquid goes into the vent
  • Spill of process liquid
Safeguards
  • Level LT-1901, LIC-1901
Action
None
Low levelDraft
Causes
  • Feed stops
Consequences
  • Outlet pump runs dry and is damaged
Safeguards
  • Level LT-1901, LIC-1901
Action
None
High pressureDraft
Causes
  • Outlet blocked (valve closed)
  • External fire
Consequences
  • V-1901 over its design pressure (FV / 3.5 barg)
Safeguards
None on the drawings
Action
  • Check whether V-1901 needs a relief valve