Safety Studio

Prepares the HAZOP from the drawings and checks the relief valves. It saves prep time; the team still runs the review and signs off every row. Legal responsibility for safety stays with the plant.

HAZOP ExcelCSV
V-2101 gas-liquid separator
PID-2101 · design pressure 10 barg · feed about 17.3 m3/h (quick simulation)
No flowDraft
Causes
  • Hand valve on the inlet left closed
Consequences
  • Downstream of V-2101 runs short of feed
Safeguards
  • Level indication LT-2101B, LIC-2102
Action
None
More flowDraft
Causes
  • Upstream pump running faster than normal
Consequences
  • V-2101 overfills
  • Downstream equipment overloaded
Safeguards
  • Level control LT-2101B, LIC-2102
Action
None
High levelDraft
Causes
  • LV-2101 fails closed
  • PV-2108 fails closed
  • HV-210104 left closed
  • HV-220101 left closed
  • Outlet pump stops
Consequences
  • V-2101 overflows or liquid goes into the vent
  • Spill of process liquid
Safeguards
  • Level LT-2101B, LIC-2102
Action
None
Low levelDraft
Causes
  • LV-2101 fails open
  • PV-2108 fails open
  • Feed stops
Consequences
  • Outlet pump runs dry and is damaged
Safeguards
  • Level LT-2101B, LIC-2102
Action
None
High pressureDraft
Causes
  • Outlet blocked (valve closed)
  • External fire
Consequences
  • V-2101 over its design pressure (10 barg)
Safeguards
  • Pressure control PT-2108, PIC-2108
Action
  • Check whether V-2101 needs a relief valve